Principle of Operation

IP5100 type IP5100 principle of operation
IP5000 principle of operation
When the input pressure applied to the SIG port of the
positioner increases, bellows q press balance lever w to the
left. As this movement moves flapper r to the left through
connecting spring e, the gap between nozzle t and flapper
r widens, and the nozzle back pressure of pilot valve y
drops. As a result, the pressure balance in the constant
pressure chamber is broken, and exhaust valve !3 presses
inlet valve B !4 to the right, thus opening inlet port B. Then,
output pressure OUT1 rises, and driven diaphragm u moves
downward.

Series Port size Supply air pressure (MPa) Input pressure (MPa)
IP5000/5100 Rc1/4 0.14 to 0.7 0.02 to 0.1